Abstract
The cascaded H-bridge (CHB) low-capacitance StatCom (LC-StatCom) has a limited operating area in the inductive region compared to a conventional StatCom's V-I characteristic. This limitation for operation in the inductive region is considered to be the biggest disadvantage of CHB LC-StatCom. In this paper, the effect of adding parallel and series reactors on the LC-StatCom system's V-I characteristic is analyzed. Then, a new configuration, which fully compensates for the lost operating area of the LC-StatCom, is introduced. A scaled down single-phase seven-level laboratory prototype is used to confirm practicability of the proposed system.
Original language | English |
---|---|
Article number | 7786824 |
Pages (from-to) | 8338-8348 |
Number of pages | 11 |
Journal | IEEE Transactions on Power Electronics |
Volume | 32 |
Issue number | 11 |
DOIs | |
Publication status | Published - Nov 2017 |
Externally published | Yes |
Bibliographical note
Publisher Copyright:© 1986-2012 IEEE.
ASJC Scopus Subject Areas
- Electrical and Electronic Engineering
Keywords
- Cascaded H-bridge
- low-capacitance (LC)-StatCom
- reactive power compensation
- thin dc capacitor