Abstract
Due to high penetration of distributed generation units in power system, fault ride through (FRT) capability is one of the new requirements of the medium-scale grid-tied photovoltaic power plants (PVPPs). This paper proposes and investigates a control strategy for the neutral-point-clamped (NPC) inverter in order to inject proper unbalanced reactive currents to the grid during unbalanced grid faults. The proper unbalanced current injection reduces negative sequence of grid voltages and currents. The current references are scaled up/down individually, based on the grid phase rms voltages and inverter nominal current. The performance of the implemented control algorithm is investigated on a 150-kVA PVPP connected to 12.47-kV medium-voltage grid simulation model under various voltage sag conditions. Results from an experimental setup of grid-tied NPC inverter are presented in order to demonstrate the effectiveness of the proposed unbalanced current injection algorithm.
Original language | English |
---|---|
Title of host publication | ECCE 2016 - IEEE Energy Conversion Congress and Exposition, Proceedings |
Publisher | Institute of Electrical and Electronics Engineers Inc. |
ISBN (Electronic) | 9781509007370 |
DOIs | |
Publication status | Published - 2016 |
Externally published | Yes |
Event | 2016 IEEE Energy Conversion Congress and Exposition, ECCE 2016 - Milwaukee, United States Duration: Sept 18 2016 → Sept 22 2016 |
Publication series
Name | ECCE 2016 - IEEE Energy Conversion Congress and Exposition, Proceedings |
---|
Conference
Conference | 2016 IEEE Energy Conversion Congress and Exposition, ECCE 2016 |
---|---|
Country/Territory | United States |
City | Milwaukee |
Period | 9/18/16 → 9/22/16 |
Bibliographical note
Publisher Copyright:© 2016 IEEE.
ASJC Scopus Subject Areas
- Control and Systems Engineering
- Electrical and Electronic Engineering
- Energy Engineering and Power Technology
- Control and Optimization
Keywords
- Fault-ride-through capability
- photovoltaic power plant
- proportional resonant controller
- three-dimensional space vector modulation
- three-leg four-wire grid connected neutral-point-clamped inverter
- unbalanced reactive current injection